Table 417:
TEIGGIO Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the warning
limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the alarm
limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the overflow
limit
ACCTIME
REAL
Integrated elapsed time in seconds
13.10.5
Settings
Table 418:
TEIGGIO Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
0 - 1
-
1
1
Disable/Enable Operation
tWarning
1.00 - 999999.99
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.99
s
0.01
1200.00
Time limit for alarm supervision
13.10.6
Operation principle
The elapsed time integrator (TEIGGIO) provides
•
time integration, accumulating the elapsed time when a given binary signal has been
high.
•
blocking and reset.
•
supervision of limit transgression and overflow.
•
retaining of the integrated value if any warning, alarm or overflow occurs.
Figure
describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.
1MRK 506 335-UUS A
Section 13
Logic
571
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...