Table 25:
ZQMPDIS (21) Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip
TR_A
BOOLEAN
Trip signal for L1
TR_B
BOOLEAN
Trip signal for L2
TR_C
BOOLEAN
Trip signal for L3
TRZ1
BOOLEAN
Trip signal Zone1
TRZ2
BOOLEAN
Trip signal Zone2
TRZ3
BOOLEAN
Trip signal Zone3
TRZ4
BOOLEAN
Trip signal Zone4
TRZ5
BOOLEAN
Trip signal Zone5
PICKUP
BOOLEAN
Pickup
PU_A
BOOLEAN
Start signal for L1
PU_B
BOOLEAN
Start signal for L2
PU_C
BOOLEAN
Start signal for L3
PU_Z1
BOOLEAN
Start signal Zone1
PU_Z2
BOOLEAN
Start signal Zone2
Z3_PU
BOOLEAN
Start signal Zone3
Z4_PU
BOOLEAN
Start signal Zone4
Z5_PU
BOOLEAN
Start signal Zone5
6.1.5
Settings
Table 26:
ZQMPDIS (21) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
CvtFltr
Disabled
Enabled
-
-
Enabled
Enable CVT Filtering
LineAng
0.00 - 90.00
Deg
0.01
80.00
Line impedance angle in degrees, common for
all zones
KNMag
0.000 - 3.000
-
0.001
0.000
Common ground compensation factor
magnitude for Zone 2, 3, 4 & 5
KNAng
-180 - 180
Deg
1
-15
Common ground compensation factor angle
for Zone 2, 3, 4 & 5
IMinPUPG
10 - 30
%IB
1
15
Minimum operating phase current for phase to
ground loops, % of IBase
IMinPUPP
10 - 30
%IB
1
15
Minimum operating phase current for phase to
phase loops, in % of IBase
Table continues on next page
1MRK 506 335-UUS A
Section 6
Impedance protection
93
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...