80 Planning the electrical installation
Supplying power for the auxiliary circuits
Supply the inverter with rated auxiliary voltage. Protect the supply according to local
regulations with, eg, fuses and/or fault current breakers. Do not connect any additional
appliances to the inverter without consulting with ABB.
Implementing the low voltage ride-through function
The user can define by parameters when the inverter must stay connected to the grid (ie,
the depth and length of the grid voltage transient). The user can also define how much the
inverter supports the grid with capacitive reactive current during the grid voltage transient.
For more information, see
PVS800 central inverters firmware manual
(3AUA0000058422
[English]).
If a low voltage ride-through function is used with the PVS800-57-100kW-A, PVS800-57-
250kW-A or PVS800-57-315kW-B inverters, the auxiliary power supply must be
uninterruptible (that is, the auxiliary voltage is not allowed to have voltage dips). Use of an
external UPS device (uninterruptible power supply) is recommended in that case.
Supplying circuits from the AC output of the inverter
If the AC output of the inverter is used for supplying any circuits, provide galvanic isolation
as shown in the diagram below. A denotes other equipment and B supplying auxiliary
circuit of the inverter. See also
Connecting the external power supply cable for the
. For instructions on selecting the transformer, see section
on page
.
PVS800-57
A
High voltage / Low voltage
PVS800-57
Q10
B
L N PE
High voltage / Low voltage
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...