Planning the electrical installation 77
Recommended AC output power cable types
The power cable types that can be used for the inverter AC output are represented below
Not allowed power cable types
Selecting the control cables
General rules
All control cables must be shielded.
Use a double-shielded twisted pair cable for analog signals. Employ one individually
shielded pair for each signal. Do not use common return for different analog signals.
A double-shielded cable is the best alternative for low-voltage digital signals but single-
shielded twisted pair cable (Figure b) is also usable.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. The shield must meet the requirements of IEC 61439-1, see
above. Check with local / state / country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. A separate PE conductor is required if the shield does not
meet the requirements of IEC 61439-1, see above.
Symmetrical shielded cable with three phase conductors and symmetrically
constructed PE conductor, and a shield. The PE conductor must meet the
requirements of IEC 61439-1.
A four-conductor system (three phase conductors and a protective conductor on a
cable tray).
WARNING!
Ground all conductive cable supports, cable clamps and
individual conductive items close to cables, such as cable trays. A
dangerous
voltage can become present on the non conductive outer
sheath of the cable. This can cause injury or death.
Symmetrical shielded cable with individual shields for each phase conductor is not
allowed on any power cabling.
PE
PE
PE
PE
PE
a
A double-shielded twisted pair cable
b
A single-shielded twisted pair cable
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...