118 Maintenance
Replacing the inverter module (frames R8i, 2 × R8i,
3 × R8i)
WARNING!
Obey the safety instructions, page
. If you ignore the instructions,
physical injury or death, or damage to the equipment can occur.
WARNING!
If you ignore these instructions, physical injury or death, or damage to
the equipment can occur.
•
Use extreme caution when manoeuvering the inverter module. Extend the support
legs of the module when it is removed from the cabinet! Do not tilt the module! The
module is heavy and has a high center of gravity. It topples over easily if handled
carelessly.
•
Lift the module by the upper part only using the lifting hole(s) at the top!
•
Do not use the ramp with plinth heights over 50 mm.The ramp supplied with the
inverter is designed for a plinth height of 50 mm (the standard plinth height of ABB
cabinets). Tighten the four fastening bolts of the ramp carefully.
Extracting the module from the cubicle
1. Stop the inverter and do the steps in section
Precautions before electrical work
page
before you start the work.
2. Open the cubicle door.
3. Remove any shrouds that protect the busbars and cable entries.
4. Open the transparent cover on the front of the inverter module (the rightmost module)
and disconnect the fiber optic cables. Move the cables aside.
5. Remove the L-shaped DC busbars on top of the module.
6. Disconnect the terminal block (X50) next to the DC busbars.
7. Remove the two module fastening screws (7a) at the top. At the base of the module,
loosen the two fastening bolts (7b) but leave them in place; lift the bracket (7c) and
fasten it into the up position carefully.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...