Planning the electrical installation 79
Separate control cable ducts
Implementing short-circuit and thermal overload
protection
Protecting the inverter and AC output cable in short-circuit
situations
The inverter is equipped with internal AC fuses which restrict inverter damage in case of a
short-circuit inside the inverter. Install external protection (such as fuses) according to local
regulations, appropriate AC line voltage and the rated current of the inverter to protect the
AC output cable.
Protecting the photovoltaic generator and DC input cable in short-
circuit situations
The input DC fuses or optional DC input miniature circuit breakers (H377) protect
the inverter DC circuit and the DC input cables in a short-circuit situation when the cable is
dimensioned according to inverter nominal DC current and fuse and breaker ratings. See
section
on page
for the fuse and breaker ratings.
To protect inverters delivered without input DC fuses (0F291), follow the
instructions in section
Instructions for inverters delivered without input DC fuses (option
on page
.
Note
: The inverter does not protect the photovoltaic generator. Install adequate protection
devices to, for example, each string.
Protecting the inverter and the AC output cable against thermal
overload
The inverter protects itself and the AC output cable against thermal overload when the
cable is dimensioned according to the nominal current of the inverter. No additional
thermal protection devices are needed.
24 V
24 V
230 V
Lead 24 V and 230 V (120 V) control
cables in separate ducts inside the
cabinet.
Not allowed unless the 24 V cable is
insulated for 230 V (120 V) or insulated
with an insulation sleeving for 230 V
(120 V).
(120 V)
230 V
(120 V)
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...