124 Technical data
Altitude derating
The inverter load capacity (current and power) decreases if the installation site altitude
exceeds 1000 metres (3300 ft). The derating is 1% for every 100 m (328 ft). For the
maximum installation site altitude, see section
on page
.
Temperature rating curves
The load capacity (current and power) decreases if the ambient temperature exceeds the
nominal ambient temperature.
Temperature rating of types -0100kW-A and -0250kW-A
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F), the rated output current is
decreased as shown below.
+30 °C
+86 °F
100
90
80
%
+40 °C
+104 °F
+50 °C
+122 °F
T
+55 °C
+131 °F
-15 °C
+5 °F
-5 °C
+41 °F
...
0
...
Nominal ambient temperature
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...