Technical data 147
CE marking
A CE mark is attached to the inverter to verify that the unit follows the provisions of the European Low Voltage
and EMC Directives.
Compliance with the European Low Voltage Directive
The compliance with the European Low Voltage Directive has been verified according to standard EN 62109.
Compliance with the European EMC directive
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within
the European Union. EMC standards EN 61000-6-2:2005 and EN 61000-6-4:2007 cover requirements stated
for electrical and electronic apparatus intended for use in industrial environments.
Compliance with EMC standards EN 61000-6-2:2005 and
EN 61000-6-4:2007
EMC stands for
E
lectro
m
agnetic
C
ompatibility. It is the ability of electrical/electronic equipment to operate
without problems within an electromagnetic environment. Likewise, the equipment must not disturb or interfere
with any other product or system within its locality.
Applicable standards and requirements
The inverter complies with the standards below.
IEC/EN 62109-1:2010
Safety of power converters for use in photovoltaic power systems Part 1:
General requirements
IEC/EN 62109-2:2011
Safety of power converters for use in photovoltaic power systems Part 2:
Particular requirements for inverters
The inverter complies with the standard when the inverter and the
photovoltaic array are installed and used inside a closed electrical operating
area. Then, the inverter does not need to comply with subclauses 4.8.2.1,
4.8.2.2, 4.8.3.2, 4.8.3.4, and 4.8.3.5.1b. However, the inverter complies with
subclauses 4.8.2.1 and 4.8.2.2.
EN 50530:2010
Overall efficiency of photovoltaic inverters
IEC 60529:1989 /
EN 60529:1991
Degrees of protection provided by enclosures (IP code)
IEC/EN 61000-6-2:2005
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards –
Immunity for industrial environments
IEC/EN 61000-6-4:2007
Electromagnetic compatibility (EMC) – Part 6-4: Generic standards –
Emission standard for industrial environments
IEC 61683:1999
Photovoltaic systems – Power conditioners – Procedure for measuring
efficiency
IEC 61000-3-12:2011
Electromagnetic compatibility (EMC) – Part 3-12: Limits – Limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and <75 A per phase
Note:
The inverter complies with the standard when its output power is 20%
of the nominal power or greater. When the output power is less than 20% of
the nominal power, the short-circuit ratio R
sce
= 250.
For the rest of the applicable standards and grid codes, go to
on the Internet.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...