40 Operation principle and hardware description
Descriptions of symbols
Symbol
Terminal/Component
Description/Operation
1
DC input terminals
The solar generator is connected to the inverter DC input terminals
with busbars and fuse links.
2
AC output
The AC output terminals connect the inverter to the low-voltage AC
power system.
3
Auxiliary control
voltage input
The customer supplies 230 V AC 1-phase auxiliary control voltage to
the inverter circuit boards, cooling fans and contactor control circuits.
For other voltages, see section
External 100 V AC, 115 V AC or
200 V AC auxiliary power supply (oG396, +G397 and
+G398)
on page
.
4
Transformer
The transformer connects the inverter AC side to the low-voltage or
medium-voltage distribution network.
5
Junction box power
supply (G410)
The inverter supplies power to the junction box through terminal X21.
Max 6 A. Fault current protected.
A20
Grounding board (with
oF282 and
+F283)
Provides fuse protection and current monitoring. See section
Positive or negative pole grounding (oF282 and +F283)
page
.
A50
Varistors
For overvoltage protection.
C11
C16
EMC filter capacitor
Reduces electromagnetic interference.
F1.1
F1.4
F1.7
AC fuses
Protect the inverter module and main circuit components.
F2.1
F2.3
F2.5
Inverter DC fuses
Protect the inverter module.
F3.x
Input DC fuses
Protect the DC input connections. The exact number of the fuses
depends on the number of the DC input connections.
F50
F51
F52
Overvoltage
protection devices
(F50 with option
+F263 only)
Devices for overvoltage protection against, for example, climatic
overvoltages caused by lightning strikes.
K1.1
K1.2
K1.3
AC contactors
The inverter controls the AC contactor according to the operational
state.
K2.1
K2.2
K2.3
DC contactors
The inverter controls the DC contactor according to the operational
state. The solar generator is disconnected from the inverter when
needed.
K19.1
K19.2
K19.3
R1.1
R1.2
R1.3
F19.1
F20.1-6
Charging circuit
The inverter controls the charging contactors after receiving a start
command.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...