Operation principle and hardware description 37
Q1
AC main switch-
disconnector
Hand-operated switch which connects the inverter to the electrical
power system.
The AC main switch-disconnector can be operated at all times. If it is
operated during operation, the inverter will trip as the grid
disappears.
Q2
DC main switch
Hand-operated switch which connects the inverter to the solar
generator.
Q10
Auxiliary control
voltage switch
Hand-operated switch which connects the auxiliary control voltage to
the inverter.
T10
Auxiliary voltage
transformer (with
oG396,
+G397, +G398 and
+G415)
Provides auxiliary voltage for the inverter circuit boards, cooling fans
and contactor control circuits.
U1
U3
Inverter module
Converts the DC voltage to AC voltage. The operation is controlled
by switching the IGBTs.
U2
U4
LCL filter
Smooths the current and voltage waveform.
Z1.1-3
Z2.1-3
Common mode filter
The filter reduces common mode voltages and currents in the solar
generator and inverter main circuit and AC output.
Z10
EMC filter (option
+E216)
EMC filter for low voltage distribution networks.
Symbol
Terminal/Component
Description/Operation
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...