146 Technical data
Auxiliary circuit power consumption
The auxiliary circuit must be supplied by the customer galvanically separated
from inverter output.
Inverter type
Total in running max.
(W)
Total in stand-by (W)
Additional
consumption in stand-
by (G300)
(max. W)
PVS800-57-0100kW-A
310
60
150
PVS800-57-0250kW-A
310
60
250
PVS800-57-0315kW-B
310
60
250
PVS800-57-0500kW-A
490
65
350
PVS800-57-0630kW-B
490
65
350
PVS800-57-0875kW-B
650
65
450
PVS800-57-1000kW-C
650
65
450
Notes:
• The values above do not include the cooling fans of the inverter modules.
Their power is taken from the solar generator.
• Every additional incoming cubicle increases the auxiliary power
consumption by 50 W in PVS800-57-0100kW-A…PVS800-57-0630kW-B
and by 25 W in PVS800-57-0875kW-B…PVS800-57-1000kW-C.
• The actual consumption depends on the options installed.
• G300: The actual power consumption depends on temperature.
• G410: Maximum power consumption 20 W per junction box.
• The auxiliary circuit has to be protected with 16 A gG fuses. See the circuit
diagrams delivered with the inverter.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...