130 Technical data
Fuses for inverters delivered without input DC fuses (option
+0F291)
The table below shows the rated DC current for selecting the input DC fuses (see the next
table) as per the number of the DC input connections to the solar generator.
The table below shows the recommended input DC fuse types.
For other fuses, contact
ABB.
No. of DC input
connections
Rated current for the input DC fuses (A)
-0250kW-A
-0315kW-B
-0500kW-A
-0630kW-B
-0875kW-A
-1000kW-A
2
400 A
400 A
-
-
-
-
3
315 A
355 A
-
-
-
-
4
250 A
250 A
400 A
400 A
-
-
5
200 A
200 A
400 A
400 A
-
-
6
160 A
200 A
355 A
355 A
-
-
7
160 A
160 A
315 A
315 A
-
-
8
160 A
160 A
250 A
250 A
400 A
400 A
9
-
-
250 A
250 A
355 A
355 A
10
-
-
200 A
200 A
315 A
315 A
11
-
-
200 A
200 A
315 A
315 A
12
-
-
200 A
200 A
250 A
250 A
13
-
-
160 A
160 A
250 A
250 A
14
-
-
160 A
160 A
250 A
250 A
15
-
-
160 A
160 A
200 A
200 A
16
-
-
-
-
200 A
200 A
17
-
-
-
-
200 A
200 A
18
-
-
-
-
200 A
200 A
19
-
-
-
-
160 A
160 A
20
-
-
-
-
160 A
160 A
Rated DC fuse
current of the
inverter
(A)
Recommended input DC fuses
400 A
PV-400AF3
355 A
PV-355AF3
315 A
PV-315AF3
250 A
PV-250AF2
200 A
PV-200AF2
160 A
PV-160AF2
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...