136 Technical data
AC output connection specification
Voltage
Types -0100kW-A, -0250kW-A and -0500kW-A: 300 V AC 3-phase
± 10%
Types -0315kW-B, -0630kW-B and -0875kW-B: 350 V AC 3-phase
± 10%
Type -1000kW-C : 400 V AC 3-phase
± 10%
Allowed electrical system
type
3-phase IT (ungrounded) system. Galvanic isolation for each inverter is
needed.
Transformer
The transformer must be suitable for IGBT-based inverter use with high d
u
/d
t
values against the ground. Dedicated low-voltage winding is needed for each
inverter. Static screen between windings with proper dimensioning is
needed.
For details on selecting the transformer, see
page
Short-circuit withstand
strength (IEC 60439-1)
Type -0100kW-A: Maximum allowable prospective short-circuit current is
10 kA when protected by fuses given in fuse tables.
Types -0250kW-A … -1000kW-C: Maximum allowable prospective short-
circuit current is 50 kA when protected by fuses given in fuse tables.
When
temporary
grounding for work is applied (the grounding cables are
connected to the connecting knobs of the AC and DC busbars and PE of the
inverter): the maximum allowable prospective short-circuit current is
decreased to 25 kA / 1 s. If the connected grounding cables and clamps are
not equivalent to the prospective short-circuit rating of the inverter, the total
rating will be lower.
Frequency
48 to 63 Hz withstand with normal dimensioning (grid-compliance may
require disconnection at smaller values.) Maximum rate of change 17%/s
Imbalance
Max.
± 3% of nominal phase to phase AC line voltage
Voltage dips
Max. 25%
Note:
If the inverter is expected to survive voltage dips (low-voltage ride-
through), auxiliary power supply must be ensured, for example, by an
uninterruptible power supply.
Fundamental power factor
(cos phi
1
)
1
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...