224 Technical specifications
Manual Power Quality Filter PQFM
(Voltage group V1)
Unit rating: 100 A
IP00: 180 kg
Network voltage: 208 V
≤
Ue
≤
480 V
(Voltage group V1)
Unit rating: 130 A
IP21: 260 kg
IP00: 180 kg
Network voltage: 208 V
≤
Ue
≤
480 V
(Voltage group V1)
Unit rating: 150 A
IP21: 260 kg
IP00: 180 kg
Color
RAL 7035 (light gray)
Mechanical installation
Floor fixation, lifting lugs provided.
Cable entry method
Plate version: bottom or top cable entry
Cubicle version: bottom cable entry, optional top cable
entry cable feed though
Common/top cable entry cubicle on request
CT requirements
3 CTs are required (Class 1.0 or better)
Filter burden: 5 VA for upto 8 units
15 VA burden for up to 30 m of 2.5 mm² cable
5 A secondary rating
CTs must be installed in closed loop configuration
Airflow requirements
A minimum of 700 m³/h cooling air has to be supplied to
each cubicle.
Network voltage characteristics
Network voltage ratings
208 V
≤
Ue
≤
480 V between phases (Voltage group V1)
480 V < Ue
≤
690 V between phases (Voltage group V2), CE
versions
480 V < Ue
≤
600 V between phases (Voltage group V2),
cULus versions
Network voltage tolerance
+/- 10 %
Network frequency
50 Hz or 60 Hz
Network frequency tolerance
+/- 5 %
Maximum rate of frequency variation
20%/s
Maximum phase jump of network
voltage
30°
Network voltage distortion
Maximum 20% phase to phase
Minimum network fault level
1 MVA
Voltage notch limits
According to IEEE519-1992, dedicated systems category
Notch depth:
≤
50%
Notch area:
≤
76*U V*
µ
s
Connection requirement:
z
load
(%)
≥
S
load
/S
trafo
* z
trafo
(%)
where: S
load
: Notch producing load power