Manual Power Quality Filter PQFM
Upon Reception 11
Remarks:
(a) Locations with normal levels of contaminants, experienced in urban areas with industrial
activities scattered over the whole area, or with heavy traffic. Also applies to locations with
immediate neighborhood of industrial sources with chemical emissions.
(b) Locations without special precautions to minimize the presence of sand or dust. Also
applies to locations in close proximity to sand or dust sources.
3.4 Identification tag
Each PQFM is fitted with nameplates for identification purposes.
For cubicle versions, the main filter nameplate is located at the top of the master panel
door, at the outside. Other unit identification nameplates may be present at the inside
of the cubicle.
For IP00 / plate versions of filter, the nameplate is fixed on the top plate of the filter
plate.
The nameplate information should always remain readable to ensure proper
identification during the whole life of the filter. The main filter nameplate includes the
filter type, the nominal voltage range and frequency as well as a serial number, the DSP
software version and an ABB internal article code.
Before connecting the filter to an already existing master, the DSP and
µ
c software
versions of both filters have to be checked. If the versions are different, contact your
ABB representative.
3.5 Storage
PQFM packing is made for a storage period of maximum six months (transport time
included from the dispatch date out of the ABB factory in Belgium). Packing for a longer
storage period can be done on request.
If your PQFM is not installed once unpacked, it should be stored in a clean indoor, dry,
dust free and non-corrosive environment. The storage temperature must be between -
25°C (-13°F) and 70°C (158°F) with a maximum relative humidity of 95%, non-condensing.
Table 2: Maximum allowed ambient conditions for storage
Storage (in the protected package)
Temperature
-25 to 70°C (-13 to 158°F)
Relative humidity
Max. 85%
Contamination levels (IEC 60721-3-
3)
Chemical class 3C3
(a)
Mechanical class 3S3