Operating instructions 187
the remote control mode has to be deactivated. More information about the
remote control functionality is given in
Section 6.12.1
and
Section 7.9.1.4
.
−
If the hardware lock and/or the Communication lock has/have been engaged, the
filter cannot be started nor stopped. In order to see which lock(s) has/have been
engaged push
when the ‘start/stop’ menu is highlighted. A message will
appear to indicate which lock(s) has/have to be disengaged. If authorized,
disengage the relevant lock.
•
The hardware lock can be disengaged by pushing the blue button present
at the bottom rear of the PQF-Manager. More information on the filter
menu locking facilities is given in
Section 7.6
.
•
The Communication lock can be engaged in the menu [/Welcome/User
interface/Communication] by ticking the “check box”. More information
on the Communication lock is available in the document
“2GCS212013A0050-RS-485 Installation and Start-up guide”.
When power is applied to the filter and it is started, the following startup sequence is
conducted:
Figure 101: Filter start-up sequence when power is applied and the start command is given
In
it may be seen that:
−
The fan starts running and the DC capacitors charge as soon as the auxiliary circuit
power is switched on.
−
The start-up sequence consists of the DC capacitors voltage check, the closure of
the filter main contactor and the starting of the IGBTs
.