Manual Power Quality Filter PQFM
Commissioning instructions 181
Project:
LV Active Filters PQF
Issued by:
Commissioning report
Date:
Page 4 of 7
Remarks:
(a)
Refer to
Sections 8.5
.
and
of the manual for more information on this topic.
(b)
Navigate with the PQF-Manager to [/Welcome/Settings/Commissioning].
(c)
Encircle the correct setting. Negative values imply inversed CT orientation or cabling.
(d)
Navigate with the PQF-Manager to [/Welcome/Settings/Customer set./Digital inputs].
(e)
Navigate with the PQF-Manager to [/Welcome/Settings/Customer set./Digital outputs].
(f)
Navigate with the PQF-Manager to [/Welcome/Settings/Customer set./Warnings].
(g)
Navigate with the PQF-Manager to [/Welcome/Settings/Customer set./Alarms].
8.11.4 Testing (with load)
Before starting the filter
OK/NOK
–
Deselect all harmonics and reactive power/balancing
(a)
Start the filter
(b)
While the filter is running(c)
–
If harmonic load is present, select for example the 11
th
harmonic
–
Check the line current (Irms, 11
th
harmonic level and waveforms)
–
If harmonic load is not present, generate static capacitive power
–
Check the filter currents (fundamental current level)
Set up the user requirements for harmonics and reactive power/balancing
(d)
–
Check the line currents (Irms, THDI and waveforms)
–
Check the line voltage (Vrms, THDV and waveforms)
Remarks:
(a)
Refer to
of the manual for more information on this topic.
(b)
Refer to
of the manual for more information on this topic.
(c)
Refer to
of the manual for more information on this topic.
(d)
Refer to
Section 8.10
of the manual for more information on this topic.