Error
messages
D184B097U02
FV4000 / FS4000
91
9.2
Error description
Error no. Plain text message
Priority
Description
Possible cause
Troubleshooting
Steam
temperature
< 55 °C (131 °F)
Increase steam
temperature
0 Steam
calculation 7
Mass flow for
saturated steam
calculated incorrectly
Steam
temperature
> 370 °C (698 °F)
Reduce steam
temperature
1 Front
End 1
Problem affecting
preamplifier board
-
Replace transmitter
plug-in module /
Contact ABB Service
2 Not
assigned -
-
-
-
Measuring range
too small
Increase "Qmax!"
measuring range
3
Flow > 3 %
2
The value set in
Qmax is being
exceeded by more
than 3 %
Flow too large
Reduce flow
4 Not
assigned -
-
-
-
5 M
database 0
Main database
damaged beyond
repair, loss of
transmitter's internal
database
Reduce flow
Replace meter and
switch back on, replace
transmitter plug-in
module
if necessary, contact
ABB Service
6
Meter damaged
beyond repair
1
Flowmeter damaged
beyond repair, values
displayed are invalid
-
Reprogram the meter
Pt100 faulty
Replace sensor
7 Temperature 7
Problem affecting
temperature
measurement
Wiring errors
between sensor
and transmitter
affecting VR / SR
models
Check wiring
8 Not
assigned -
-
-
-
9
Qv > 120 % of
QmaxDN
2
Maximum possible
measuring range
(QmaxDN) overshot
Flow too large
(software only)
level < A30
Reduce flow
B B
base 0
Backup database
damaged beyond
repair, loss of
external database
(sensor board)
External database
faulty
Switch the meter off
and back on again,
sensor board might be
faulty, contact ABB
Service
Summary of Contents for FS4000
Page 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 FS4000 ...
Page 116: ...Appendix 116 FV4000 FS4000 D184B097U02 ...
Page 117: ...Appendix D184B097U02 FV4000 FS4000 117 ...
Page 118: ...Appendix 118 FV4000 FS4000 D184B097U02 ...
Page 119: ...Appendix D184B097U02 FV4000 FS4000 119 ...
Page 120: ...Appendix 120 FV4000 FS4000 D184B097U02 ...
Page 125: ......