Electrical connections
46
FV4000 / FS4000
D184B097U02
5.5
Configuration of the switching output
The switching output can be configure as both a NAMUR contact and an optocoupler.
G00720
1 K
10 K
41
42
41
42
Rotary switch counterclockwise:
NAMUR contact
Rotary switch clockwise: optocoupler
Fig. 37: Switching output circuit diagram
The switching output of the transmitter is factory-configured on the basis of the order code. The
following table lists contact types and their matching order codes and Ex approval.
Order code
Ex approval
Contact type
VT40, VR40, ST40, SR40
None
optocoupler
VT41,VR41, ST41, SR41
Ex ib / Ex nA [nL]
NAMUR contact
VT42, VR42, ST42, SR42
Ex d / Ex ib / Ex nA [nL]
Optocoupler
VT43, VR43, ST43, SR43
C
FM
US
Optocoupler
VT4A, VR4A, ST4A, VR4A
II 2G EEx ia IIC T4
NAMUR contact
If necessary, the switching output can be modified subsequently should prevailing site
conditions change.
1. Disconnect the flowmeter from the line supply.
2. Unscrew the front housing cover. The lock on the cover needs to be undone first on meters
for hazardous areas.
Important
Observe the waiting times for meters for hazardous areas (see the section titled 11 „Ex
relevant specifications“.)
3. Remove the transmitter from the housing. To do this, unscrew the three Phillips head screws
and carefully take the transmitter out of the housing.
Summary of Contents for FS4000
Page 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 FS4000 ...
Page 116: ...Appendix 116 FV4000 FS4000 D184B097U02 ...
Page 117: ...Appendix D184B097U02 FV4000 FS4000 117 ...
Page 118: ...Appendix 118 FV4000 FS4000 D184B097U02 ...
Page 119: ...Appendix D184B097U02 FV4000 FS4000 119 ...
Page 120: ...Appendix 120 FV4000 FS4000 D184B097U02 ...
Page 125: ......