Ex relevant specifications
D184B097U02
FV4000 / FS4000
103
11.3.3 Medium temperatures / Temperature
classes
For the supply circuit "Terminals 31, 32" and the switching outputs
"Terminals 41, 42", cables suitable for temperatures up to T = 110 °C
(T = 230 °F) can be used without restriction.
Category 2/3G (Ex ib IIC)
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the interconnection of both circuits needs to be taken into account in
the event of a fault. Otherwise, the restricted temperature ranges
listed in the following table shall apply.
Category 2D
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the restricted temperature ranges listed in the following table shall
apply.
Ambient
temperature
2)
Max. temperature
at used
connecting cable,
"Terminals 31,
32", "Terminals
41, 42"
Max. permissible
medium
temperature
(-40) -20 ... 60 °C
(-40) -4 ... 140 °F)
110 °C (230 °F)
280 °C / 400 °C
1)
(536 °F / 752 °F)
1)
(-40) -20 ... 60 °C
(-40) -4 ... 140 °F)
240 °C (464 °F)
(-40) -20 ... 55 °C
(-40) -4 ... 131 °F)
280 °C (536 °F)
(-40) -20 ... 50 °C
(-40) -4 ... 122 °F)
320 °C (608 °F)
1)
(-40) -20 ... 40 °C
(-40) -4 ... 104 °F)
80 °C (176 °F)
400 °C (752 °F)
1)
1)
Medium temperatures > 280 °C (> 536 °F) with FV4000 Vortex flowmeter only
2)
The permissible lower limits for the ambient temperature are approval- and order-
specific (standard: -20 °C (-4 °F)).
Hazardous area
design
Maximum medium
temperature
Temperature class
80 °C (176 °F)
T6
3)
Ex d [ib] IIC
95 °C (203 °F)
T5
3)
130 °C (266 °F)
T4
195 °C (383 °F)
T3
290 °C (554 °F)
T2
Ex ib IIC
bzw.
Ex nA [nL]
400 °C (752 °F)
T1
3) Not possible for flowmeter sensor version VR42 / SR42
Change from one to two columns
11.4 FM approval design for the USA and Canada
for VT43/ST43 and VR43/SR43
(4 ... 20 mA / HART)
Important
The devices may only be operated in explosive areas if the
housing covers have been fully closed.
Designation
Explosion-proof XP/Class I/Div 1/BCD/T4 Ta = 70 °C Type 4X
Dust-ignition-
proof
DIP/Class II,III/Div 1/EFG/T4 Ta = 70 °C Type 4X
Intrinsic safety
IS/Class I, II,III/Div 1/ABCDEFG/T4 Ta = 70 °C
Entity Type 4X
Non-incendive
NI/Class I/Div 2/ABCD/T4 Ta = 70 °C Type 4X
Suitable
S/Class II,III/Div 2/FG/T4 Ta = 70 °C Type 4X
The devices must be installed in a protected environment in
accordance with the specific conditions on the test certificate.
Pollution degree 3 (see IEC 60664-1) must not be exceeded for the
macro environment of the device. The devices conform to degree of
protection IP65 / IP67. If the device is installed as intended, this
requirement is met by the housing as standard.
When connected to the line supply / not connected to the line supply,
the electrical circuits must not exceed overvoltage category III / II.
IS Entity see: SD-50-2681 (Fig. 35)
Parameters: Vmax, Imax, Pi, Li, Ci
Enclosure: Type 4X
G00674
Eex d [ib]
Ex ib
Ex nA [L]
FM
APPROVED
C
US
FM
APPROVED
C
US
FM
APPROVED
C
US
1
2
3
+
+
+
+
81
82
83
84
85
86
86
87
42
42
41
41
32
32
31
31
VR43/SR43
VT43/ST43
PA
PA
PA
Fig. 54:
Electrical connection for VT43 / ST43 and VR43 / SR43
1
Flowmeter sensor
2
Transmitter
3
Flowmeter
Flowmeter sensor wire colors
Terminal
Wire color
81 Red
82 Blue
83 Pink
84 Gray
85 Yellow
86 Green
86 Brown
87 White
Summary of Contents for FS4000
Page 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 FS4000 ...
Page 116: ...Appendix 116 FV4000 FS4000 D184B097U02 ...
Page 117: ...Appendix D184B097U02 FV4000 FS4000 117 ...
Page 118: ...Appendix 118 FV4000 FS4000 D184B097U02 ...
Page 119: ...Appendix D184B097U02 FV4000 FS4000 119 ...
Page 120: ...Appendix 120 FV4000 FS4000 D184B097U02 ...
Page 125: ......