Transmitter specifications
114
FV4000 / FS4000
D184B097U02
13 Transmitter specifications
Change from one to two columns
G00633
C/CE
Step
Data/ENTER
Data/Enter
Step
C/CE
1
2
3
Fig. 67:
Transmitter keypad and LCD display
1
Magnet sensors
2
Control buttons for direct
entry
3
Can be r/- 90 °
Measuring ranges
The full-scale value can be set at any point between the maximum
possible upper range value 1.15 x QmaxDN and 0.15 x QmaxDN.
Parameter setting
Data can be entered using 3 control buttons (not with the Ex "d"
hazardous area design) or, if the housing is sealed, directly from an
external location using a magnetic pen.
Data is entered in plain text with the display or using digital
communication via the HART protocol or PROFIBUS
PA/FOUNDATION Fieldbus.
Flow operating modes
The following operating modes can be selected dependent upon the
design purchased (with or without Pt100):
Fluid medium:
• Operating
flow
•
Mass flow with constant or temperature-dependent density
Gas/steam medium:
• Operating
flow
•
Mass flow with constant or temperature-dependent density (at
constant pressure)
•
Standard flow with constant or temperature-dependent standard
factor (at constant pressure)
•
Mass flow with saturated steam and temperature-driven density
Data backup
Counter readings and parameters for specific measuring points
backed up in FRAM (more than 10 years without supply power) in the
case of shutdown or should the supply voltage fail.
Damping
Configurable from 1 ... 100 s, corresponds to 5
τ
.
Q
v min
(low flow)
Configurable between 2 ... 25 % of QmaxDN (max. operating flow per
nominal size). The actual low flow is determined by application and
installation.
Function tests
Software-internal function tests can be used to test individual internal
modules. For the purpose of commissioning and testing, the current
output (4 ... 20 mA design) or the digital output signal (fieldbus
designs) can be simulated in line with flowrates selected by the user
(manual process control). The switching output can also be controlled
directly for the purpose of function testing.
Electrical connection
Screw-type terminals, plug-in connection on PROFIBUS PA (option)
cable gland: -standard., Ex "ib" / Ex "ia": M20 x 1.5; NPT 1/2 ” -Ex d”:
NPT 1/2”
Ingress protection
IP 67 to EN 60529
Display
High-contrast LCD display, 2 x 8-digit (4 ... 20 mA design) or 4 x 16-
digit (PROFIBUS PA / FOUNDATION Fieldbus design). Shows the
instantaneous flowrate along with the totalized flow or temperature of
the medium (option).
On the 4 ... 20 mA design, the multiplex function enables 2 values
(e.g., flowrate and totalized flow) to be displayed virtually in parallel.
Up to 4 values can be displayed on the fieldbus design.
Switching output terminals 41 / 42
(standard on all designs)
The function can be selected via the software:
-
Max./min. alarm for flow or temperature
- System
alarm
-
Pulse output: fmax: 100 Hz; ton: 1 ... 256 ms
Contact type:
-
Standard and Ex "d": Optocoupler UH = 16 ... 30 V
IL = 2 ... 15 mA
-
Ex "ib" / Ex "ia": Configured as NAMUR contact
EMC protection
The flowmeter corresponds to NAMUR recommendations NE21.
Electromagnetic compatibility of equipment for process and lab
control technology 5/93 and EMC Directive 2004/108/EC (EN 61326-
1). Note: EMC protection and protection against accidental contact
are limited when the housing cover is open.
Change from one to two columns
Summary of Contents for FS4000
Page 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 FS4000 ...
Page 116: ...Appendix 116 FV4000 FS4000 D184B097U02 ...
Page 117: ...Appendix D184B097U02 FV4000 FS4000 117 ...
Page 118: ...Appendix 118 FV4000 FS4000 D184B097U02 ...
Page 119: ...Appendix D184B097U02 FV4000 FS4000 119 ...
Page 120: ...Appendix 120 FV4000 FS4000 D184B097U02 ...
Page 125: ......