Functional Software description
14
DCS 500 Software Description
Messages, which may come up, if a SDCS-CON2 and DRIVE
_MODE = 3 [ARM. AUTOTUNING] autotuning of armature cur-
rent controller is used:
49 = IF AT START ?
Field current does not reach reference
within 10s, when the selftuning is
started
50 = OHMIC LOAD
Ohmic load not determined
51 = IACT FEEDBACK
Current feedback is less than current
reference during measurement of ar-
mature resistance. Current limits are
lower than the limit for continous cur-
rent flow or lower than 20%.
52 = CURRENT CURVE
Bad current curve. Fuse
blown,thyristor not firing or no motor
load.
53 = RUN COMMAND ?
Wrong starting conditions. The drive is
running when the autotuning is started
or run command is not given within 20
s after start of autotuning.
54 = TOO HIGH SPEED
Too high speed during autotuning
.Speed greater than 1% or EMF grea-
ter than 15%.
55 = INDUCTANCE
Inductance cannot be determined. Fu-
se blown,
thyristor not firing or no
motor load.
56 = CONT CURR LIM
Limit for continous current flow cannot
be determined.
57 = FIELD REMOVAL
The field removal takes longer time
than 10 s.
58 = STOP COMMAND
Current regulator blocking or stop
command appears during autotuning.
Messages, which may come up, if a SDCS-CON2 and DRIVE
_MODE = 5 [FEX2/3 AUTOTUN] autotuning of field current
controller with FEX2 or DCF 503/4 is used:
60 = CANNOT AUTOTUNE The field current controller cannot be
set by this function
61 = ILL START COND
Illegal start condition for field autotu-
ning