DCS500 Pin and Parameter list
A 9
AI2_CONV_MODE
Parameter of AI2-function block
( S6/16 ).
Selector for type of input signal:
0 = DISABLE
channel not in use
1 = +/-10V +/-20 mA
-10...+10V
IOB1, CON-2, IOB3
-20...+20mA
IOB1, CON-2: 500 ohms between X3:7-8
IOB3: S1:5-6 connected
2 = 4...20 mA
4 ... 20mA
IOB1, CON-2: 500 ohms between X3:7-8
IOB3: S1:5-6 connected
3 = 1 x PT100
IOB3: S5:3-4 + S2:1-2, 3-4, 5-6, 7-8
4 = 2 x PT100
IOB3: S5:3-4 + gain = 1
5 = 3 x PT100
IOB3: S5:3-4 + gain = 1
6 = PTC, BOARD IOB3
IOB3: S5:1-2 + gain = 1
7 = PTC, BOARD IOB1
IOB1, CON-2: S1: 23-24 (+10V source)
107
FB_P: E2
SC: -
HL: 7
LL: 0
D: 0
U: -
AI2_HIGH_VALUE
Parameter of AI2-function block
( S6/16 ).
Value that corresponds to upper range input signal (+10V/20mA)
108
FB_P: I2
SC: 1
HL: 32767
LL: -32768
D: 2000
U: -
AI2_LOW_VALUE
Parameter of AI2-function block
( S6/16 ).
Value that corresponds to lower range input signal (-10V/0mA/4mA)
109
FB_P: I2
SC: 1
HL: 32767
LL: -32768
D: -2000
U: -
AI3_CONV_MODE
Parameter of AI3-function block
( S11/16 ).
Selector for type of input signal:
0 = DISABLE
channel not in use
1 = +/-10V or +/-20 mA
-10...+10V
IOB1, IOB3, CON-2
-20...+20mA
IOB1, CON-2: 500 ohms between X3:9-10
IOB3: S1:7-8 connected
2 = 4...20 mA
4 ... 20mA
IOB1, CON-2: 500 ohms between X3:9-10
IOB3: S1:7-8 connected
3 = 1 x PT100
IOB3: S5:3-4, + S3:1-2, 3-4, 5-6, 7-8 conn.
4 = 2 x PT100
IOB3: S5:3-4 + gain = 1
5 = 3 x PT100
IOB3: S5:3-4 + gain = 1
6 = PTC, BOARD IOB3
IOB3: S5:1-2 + gain = 1
110
FB_P: E2
SC: -
HL: 6
LL: 0
D: 0
U: -
AI3_HIGH_VALUE
Parameter of AI3-function block
(S11/16 ).
Value that corresponds to upper range input signal (+10V/20mA)
111
FB_P: I2
SC: 1
HL: 32767
LL: -32768
D: 2000
U: -
AI3_LOW_VALUE
Parameter of AI3-function block
(S11/16 ).
Value that corresponds to lower range input signal (-10V/0mA/4mA)
112
FB_P: I2
SC: 1
HL: 32767
LL: -32768
D: -2000
U: -
Summary of Contents for DCS 500B
Page 8: ......
Page 102: ...Functional Software description 94 DCS 500 Software Description ...
Page 227: ......