Functional Software description
DCS 500 Software Description
65
•
Protections
CONVERTER_PROTE
CTION function block
Network voltage
measurement
The measurement/calculation of network voltage is based on the
nominal voltage of the converter, nominal voltage of the supply and
the voltage measurement as follows:
U NET ACT
U
U CONV V
U SUPPLY
e g
measured
(
)
*
(
)
(
)
. .
*
%
10504
10511
507
3276 500
400
4095
100
=
=
=
=
400 V supply
Note.
DCS 500B converter module is exactly the same for 400V
and 500V supply. Voltage measurement scaling is constant 500V =
4095.
U CONV V (10511)
signal value
must be 500
also for 400V
supply (software reads this value automatically from the SDCS-
PINxx board when C1, C2 or C3 modules are used).
Network under-
voltage
The nominal net voltage is defined in
U SUPPLY (507)
. The upper
limit for network undervoltage is defined in % by parameter
U NET
MIN1 (508)
. If the network voltage drops below this limit, the con-
trollers are blocked. An undervoltage trip is generated if network
voltage is not restored within the time defined by parameter
PWR
DOWN TIME (510)
. Scaling 1 == 1 ms.
The lower limit for network undervoltage is defined in % by pa-
rameter
U NET MIN2 (509)
. If the network voltage drops below this
limit, the drive is tripped immediately.
Network over-
voltage
The overvoltage limit is fixed to 130%. If this limit is exceeded, and
the situation continues for at least 10 seconds, an
OVERVOLTAGE-fault will occur. Armature overvoltage level is de-
fined in % of nominal voltage of motor by parameter
ARM OVERVOLT LEV (511)
.
Overcurrent
There is a fixed overcurrent limit for the converter, and this value
can be read out from the signal
I TRIP A (10510)
(scale 1 = 1A)
If there is a need to reduce this limit, it can be done with the pa-
rameter:
ARM OVERCURR LEV (512)
scale: 100 = nominal current of converter
I CONV A (10509)
.