DCS500 Pin and Parameter list
A 61
Group 25: FB EXECUTION
TASK1_EXEC_ORDER
Execution order of function blocks of task 1, which is executed at 5 ms interval.
2501
P: AI2
SC: -
HL: 10000
LL: 0
D: 0
U: -
TASK2_EXEC_ORDER
Execution order of function blocks of task 2, which is executed at 20 ms interval.
2502
P: AI2
SC: -
HL: 10000
LL: 0
D: 0
U: -
TASK3_EXEC_ORDER
Execution order of function blocks of task 3, which is executed at 200 ms interval.
2503
P: AI2
SC: -
HL: 10000
LL: 0
D: 0
U: -
FB_APPL_ENABLE
Selection parameter for the execution of function block application:
0:
(disabled; application blocks are not executed)
1:
(enabled; application blocks are executed).
2504
FB_P: I2
SC: 1
HL: 1
LL: 0
D: 0
U: -
FB_TASK_LOCK
Interlocking flag for function block programming via panel CDP 312 or PC tool CMT. If
function block programming is started via one tool, this one will set this flag to prevent
similar actions taking place via the other tool. This flag can be actively set by using one of
the tools to define this one being the preferred for function block programming.
0:
(disabled; locking flag is not set)
1:
(enabled; locking flag is set).
2505
FB_P: I2
SC: 1
HL: 1
LL: 0
D: 0
U: -