Functional Software description
DCS 500 Software Description
9
Analog Outputs
There are three analog output channels. Connections are made to
either SDCS-CON-2 or SDCS-IOB-3 boards. The first two outputs
(AO1 and AO2) are programmable, and the range of the outputs is
+10V...-10V. The third output is an armature current actual measu-
rement from the HW-circuit. For more detailed information, see
TECHNICAL DATA.
AO1
NOMINAL V
202
OFFSET V
203
NOMINAL VAL
204
[IN]
201
SP
ST5
Input signal
Maximum output voltage (V)
Minimum output voltage (V)
Maximum value
P1
P3
P2
10000
0
20000
Figure
9
Analog Output Function Block
Example:
If the signal SPEED ACT (12102) is used in the analog output1,
the settings are:
AO1 [IN] (201)
= 12102
AO1 NOMINAL V (202)
= 10
AO1 OFFSET V (203)
= 0
AO1 NOMINAL VAL (204)
= 20 000
With these settings the actual speed value 20000 corresponds to
+10V output voltage.
U =
out
[IN]
NOMINAL VAL
NOMINAL V + OFFSET V
Summary of Contents for DCS 500B