DCS500 Pin and Parameter list
A 5
Parameters of DCS 500
DCS/DCF 500B parameters consist of two types (parameters and inputs) and divided to
several different parameter groups. Parameters / inputs of a certain group belong to the same
functional part of the control program. Maximum number in one group is 99.
(within this manual the word
parameter
will be used for both types, parameter and input)
Every parameter is described using the same structure, which is shown by their basics below:
name
Para
meter of {
standard function block
} function block
(S11/16 ).
Expl
anation
index
data type
scal. factor
maximum
minimum
default
unit
Name
is given in the same format as it is seen on the panel.
Para
mentiones the name of the function block using this parameter; at the end of
this line the page of the software diagrams available at the end of the System
Description is given; at some parameters the software version is named this
parameter is available for the first time
Expl
description in verbal form
Index
of a parameter contains a group number and an element number. Last two
digits are the element number and other numbers before them form the
group number:
101
=> parameter group = 1, element = 01
1404
=> parameter group = 14, element = 04.
Data type
is given with a short code:
FB_I:
Input of a function block
FB_P:
Parameter of a function block
P:
Parameter
I2
16-bit signed integer
E2
Selection parameter
PB
packed Boolean value
B
Boolean value
U2
16-bit unsigned integer
C4
connection to function block output (signal) or to some parameter
Scaling factor
In this table scaling factors are presented using symbols or constants.
scaling factor (=100%)
calculation: internal to physical value
scaling factor used at (excerpt):
0.001
int.val *
0.001 [unit]
----
0.01
int.val *
0.01 [unit]
5.03, 10.18 and others
0.1
int.val *
0.1
[unit]
4.14, 17.08 and others
1
int.val *
1
[unit]
1.08, 2.02 and others
MCURR
(
4095)
int.val *
5.02 [A]
/ 4095
4.02; 14.06;
motor current in A
FCURR
(
4095)
int.val *
5.04 [A]
/ 4095
13.01, 13.05;
field current in A
VOLT
(
4095)
int.val *
5.07 [V]
/ 4095
13.11, 15.08;
voltage in V
SPEED
(
20000)
int.val *
21.03 [RPM] / 20.000
1.02, 17.01;
motor speed in RPM
CCURR
(
4095)
int.val * 105.09 [A]
/ 4095
4.09, 3604;
converter current in A
TORQ
(
4000)
int.val *
100.0 [%]
/ 4000
4.01, 13.19;
motor torque in %
CURR
(
4095)
int.val *
100 [%]
/ 4095
10.13;
current in %
FLUX
(
4095)
int.val *
100 [%]
/ 4095
10.02, 10.09;
flux in %
EMF
(
3786)
int.val *
100 [%]
/ 3786
10.03, 10.11;
motor emf in %
BI
(logic input)
not equal to 0
0
= TRUE
= FALSE
BO
(logic output)
-1
0
= TRUE
= FALSE