DCS500 Pin and Parameter list
A 58
MAX_CURR_LIM_SPD
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
The speed limit named with x where armature current limitation starts to decrease the
current limit.
2309
FB_P: I2
SC: SPEED
HL: 20000
LL: 0
D: 20000
U: rpm
MAX_CURR_LIM_N1
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
Armature current limit at speed MAX_CURR_LIM_SPD (2309).
2310
FB_P: I2
SC: MCURR HL: 16383
LL: 0
D: 16383
U: A
MAX_CURR_LIM_N2
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
Armature current limit at speed:
MAX_CURR_L 1/4*(20000 - MAX_CURR_LIM_SPD).
2311
FB_P: I2
SC: MCURR HL: 16383
LL: 0
D: 16383
U: A
MAX_CURR_LIM_N3
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
Armature current limit at speed:
MAX_CURR_L 2/4*(20000 - MAX_CURR_LIM_SPD).
2312
FB_P: I2
SC: MCURR HL: 16383
LL: 0
D: 16383
U: A
MAX_CURR_LIM_N4
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
Armature current limit at speed:
MAX_CURR_L 3/4*(20000 - MAX_CURR_LIM_SPD).
2313
FB_P: I2
SC: MCURR HL: 16383
LL: 0
D: 16383
U: A
MAX_CURR_LIM_N5
Parameter of TORQUE/CURRENT_LIMITATION-function block.
( S6/16 )
Speed dependent current limitation.
Armature current limit at speed:
20000 (nominal speed of the drive).
2314
FB_P: I2
SC: MCURR HL: 16383
LL: 0
D: 16383
U: A
20000
X + 2/4*(20000 - X)
X + 1/4*(20000 - X)
X + 3/4*(20000 - X)
X
MAX_CURR_LIM_N1
MAX_CURR_LIM_N5
MAX_CURR_LIM_N4
MAX_CURR_LIM_N3
MAX_CURR_LIM_N2
SPEED_ACT(12101)