DCS500 Pin and Parameter list
A 43
Group 15: MOTOR 2 FIELD
[F2_REF]
Input of MOTOR_2_FIELD-function block.
( S8/16 )
Field current reference for motor 2 field exciter.
1501
FB_I: C4
SC: FCURR
HL: 19999
LL: 0
D: 12512
U: -
F2_CURR_GT_MIN_L
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Tripping level of minimum field current monitoring function.
1502
FB_P: I2
SC: FCURR
HL: 4095
LL: 0
D: 2047
U: A
F2_OVERCURR_L
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Field overcurrent limit for motor 2. The default limit is 115% of nominal field current.
1503
FB_P: I2
SC: FCURR
HL: 8191
LL: 0
D: 4710
U: A
F2_CURR_TC
Parameter of MOTOR_2_FIELD-function block
(S8/16 ).
Filter time constant for actual field current measurement. (lower HL in S21.232)
1504
FB_P: I2
SC: 0.01
HL: 1000
LL: 0
D: 0
U: s
F2_KP
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Proportional gain for PI controller in the field excitation unit .
1505
FB_P: I2
SC: -
HL: 4096
LL: 0
D: 1
U: -
F2_KI
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Integral action time for PI controller in the field excitation unit .
1506
FB_P: I2
SC: 0.01
HL: 4096
LL: 0
D: 20
U: s
F2_U_AC_DIFF_MAX
Parameter of MOTOR_2_FIELD_OPTIONS-function block
(S8/16 ).
Threshold level for free-wheeling function. If two successive AC voltage measurements in
field exciter differ more than this then the 2 phase field exciter activates the free-wheeling
function. (lower HL in S21.232)
1507
FB_P: I2
SC: 1
HL: 1000
LL: 0
D: 10
U: %
F2_U_LIM_N
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Negative output voltage limitation for current controller in field excitation unit.
Minimum output voltage = -4096.
1508
FB_P: I2
SC: VOLT
HL: 0
LL: -4096
D: -4096
U: %
F2_U_LIM_P
Parameter of MOTOR_2_FIELD-function block.
( S8/16 )
Positive output voltage limitation for current controller in field excitation unit.
Maximum output voltage = 4096.
1509
FB_P: I2
SC: VOLT
HL: 4096
LL: 0
D: 4096
U: %
F2_RED.SEL
Parameter of MOTOR_2_FIELD -function block.
( S8/16 )
Enables field heating function for the motor when the RUN-command is not active.
The function is activated 10 s after the RUN-command has been removed.
0 = DISABLE
1 = ENABLE
1510
FB_P: E2
SC: -
HL: 1
LL: 0
D: 0
U: -