DCS500 Pin and Parameter list
A 99
Group 114: MOTOR 1 PROTECT.
MOT1_MEAS_TEMP
Signal of MOTOR_1_PROTECTION- function block.
( S9/16 )
Measured temperature of motor 1.
The unit of the value depends on the selection of AI_CONV_MODE (107, 110):
0 = not selected
1, 2 = value scaled by AI_HIGH_VALUE (108,111) and AI_LOW_VALUE (109,112)
3..5 = unit = degrees
6, 7 = resistance value is ohms
(but displayed in °C )
11401
FB_O: I2
SC: -
HL: -
LL: -
D: -
U: C
MOT1_CALC_TEMP
Signal of MOTOR_1_PROTECTION- function block.
( S9/16 )
Output from thermal model for motor 1.
11402
FB_O: I2
SC: -
HL: -
LL: -
D: -
U: %