Fault tracing 425
5090
STO hardware failure
Safe torque off hardware
failure.
Contact your local ABB
representative. The code contains
location information, especially
with parallel-connected inverter
modules. When converted into a
32-bit binary number, the bits of the
code indicate the following:
31…28: Number of faulty inverter
module (0…11 decimal). 1111:
STO_ACT states of control unit
and inverter modules in conflict
27: STO_ACT state of inverter
modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules
12…1 (Bits of non-existing
modules set to 1)
11…0: STO2 of inverter modules
12…1 (Bits of non-existing
modules set to 1)
5091
Safe torque off
Programmable fault:
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is broken
during start or run.
Check safe torque off circuit
connections. For more information,
see appropriate drive hardware
manual and description of
parameter
(page
).
5092
PU logic error
Power unit memory has
cleared.
Contact your local ABB
representative.
5093
Rating ID mismatch
The hardware of the drive
does not match the
information stored in the
memory unit. This may occur
eg. after a firmware update
or memory unit replacement.
Cycle the power to the drive.
Check the auxiliary code. The
auxiliary
code categories are as follows:
1 = PU and CU ratings not the
same.
Rating ID has changed.
2 = Parallel connection rating ID
has changed.
3 = PU types not the same in all
power units.
4 = Parallel connection rating ID is
active in a single power unit setup.
5 = It is not possible to implement
the selected rating with the current
PUs.
6 = PU rating ID is 0.
7 = Reading PU rating ID or PU
type failed on PU connection.
With parallel connection faults, the
format of the auxiliary code is
0X0Y. “Y” indicates the auxiliary
code category, “X” indicates the
first faulty PU channel in
hexadecimal (1…C).
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...