154 Parameters
Specifies the analog input limits to be supervised. See
parameter
.
Note:
The number of active bits in this parameters
depends on the number of inputs on the extension module.
0000 0000b
0000 0000b…0011
1111b
Activation of analog input supervision.
1 = 1
)
Selects a drive signal to be connected to digital
input/output DIO3 when parameter
is
set to
.
For the available selections, see parameter
or
)
Triggers the analog input tuning function, which enables
the use of actual measurements as the minimum and
maximum input values instead of potentially inaccurate
estimates.
Apply the minimum or maximum signal to the input and
select the appropriate tuning function.
See also the drawing at parameter
.
No action
Tuning action completed or no action has been requested.
The parameter automatically reverts to this value after any
tuning action.
0
AI1 min tune
The measured value of AI1 is set as the minimum value of
AI1 into parameter
1
AI1 max tune
The measured value of AI1 is set as the maximum value of
AI1 into parameter
2
AI2 min tune
The measured value of AI2 is set as the minimum value of
AI2 into parameter
3
AI2 max tune
The measured value of AI2 is set as the maximum value of
AI2 into parameter
4
AI3 min tune
The measured value of AI3 is set as the minimum value of
AI3 into parameter
5
AI3 max tune
The measured value of AI3 is set as the maximum value of
AI3 into parameter
6
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4
AI3 < MIN
1 = Minimum limit supervision of AI3 active (FIO-11 only).
5
AI3 > MAX
1 = Maximum limit supervision of AI3 active (FIO-11 only).
6…15
Reserved
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...