Activates the variable slope function, which controls the
slope of the speed ramp during a speed reference change.
This allows for a constantly variable ramp rate to be
generated, instead of just the standard two ramps normally
available.
If the update interval of the signal from an external control
system and the variable slope rate (
) are equal, the resulting speed reference (
) is a straight line.
This function is only active in remote control.
Off
Variable slope disabled.
0
On
Variable slope enabled (not available in local control).
1
Source selection (see
on
page
-
Defines the rate of the speed reference change when
variable slope is enabled by parameter
.
For the best result, enter the reference update interval into
this parameter.
50 ms
2…30000 ms
Variable slope rate.
1 = 1 ms
Displays the speed correction term for the load share
function with a speed-controlled follower drive.
See section
).
This parameter is read-only.
-
-30000.00
…30000.00 rpm
Speed correction term.
See par.
Follower speed
correction enable
With a speed-controlled follower, selects the source for
enabling/disabling the load share function.
See section
).
0 = Disabled
1 = Enabled
Not selected
0.
0
Selected
1.
1
No.
Name/Value
Description
Def/
FbEq16
t
Speed
reference
Speed reference
Time
A
t = update interval of signal from external control system
A = speed reference change during t
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...