Parameters 345
Saving
A user set is being saved.
2
Faulted
Invalid or empty parameter set.
3
User set 1
User set 1 has been loaded.
4
User set 2
User set 2 has been loaded.
5
User set 3
User set 3 has been loaded.
6
User set 4
User set 4 has been loaded.
7
Enables the saving and restoring of up to four custom sets
of parameter settings. See section
(page
).
The set that was in use before powering down the drive is
in use after the next power-up.
Notes:
• Hardware configuration settings such as I/O extension
module, fieldbus and encoder configuration parameters
(groups 14…16, 47, 51…56, 58 and 92…93) are forced
input/output values (such as 10.03 and 10. 04) are not
included in user parameter sets.
• Parameter changes made after loading a set are not
automatically stored – they must be saved using this
parameter.
No action
Load or save operation complete; normal operation.
0
User set I/O mode
Load user parameter set using parameters
and
1
Load set 1
Load user parameter set 1.
2
Load set 2
Load user parameter set 2.
3
Load set 3
Load user parameter set 3.
4
Load set 4
Load user parameter set 4.
5
Save to set 1
Save user parameter set 1.
18
Save to set 2
Save user parameter set 2.
19
Save to set 3
Save user parameter set 3.
20
Save to set 4
Save user parameter set 4.
21
When parameter
is set to
, selects the user parameter set together with
as follows:
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
No.
Name/Value
Description
Def/
FbEq16
Status of
source defined
by par.
Status of
source defined
by par.
User parameter
set selected
0
0
Set 1
1
0
Set 2
0
1
Set 3
1
1
Set 4
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...