352 Parameters
Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of one
winding. With a delta-connected motor,
R
S
is one-third of
the resistance of one winding.
0.00000 p.u.
0.00000
…0.50000 p.u.
Stator resistance in per unit.
-
Defines the rotor resistance
R
R
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000
…0.50000 p.u.
Rotor resistance in per unit.
-
Defines the main inductance
L
M
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000
…10.00000 p.u.
Main inductance in per unit.
-
Defines the leakage inductance
σ
L
S
.
Note: This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000
…1.00000 p.u.
Leakage inductance in per unit.
-
Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000
…10.00000 p.u
Direct axis inductance in per unit.
-
Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000
…10.00000 p.u
Quadrature axis inductance in per unit.
-
Defines the permanent magnet flux.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000
…2.00000 p.u
Permanent magnet flux in per unit.
-
Defines the stator resistance
R
S
of the motor model.
0.00000 ohm
0.00000
…100.00000 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
0.00000 ohm
0.00000
…100.00000 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
0.00 mH
0.00…100000.01 mH Main inductance.
1 = 10000 mH
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...