Fault tracing 411
A5EF
PU state feedback
State feedback from
output phases does not
match control signals.
Contact your local ABB representative.
A5F0
Charging feedback
Charging feedback
signal missing.
Check the feedback signal coming
from the charging system.
A683
Data saving to power unit An error in saving data to
the power unit.
Check the auxiliary code. See actions
for each code below.
0 An error is preventing
saving from initializing.
Cycle the power to the drive. If the
control unit is externally powered, also
reboot the control unit (using parameter
) or by cycling
its power. If the problem persists,
contact your local ABB representative.
1
2 Write error.
A684
SD card
Error related to SD card
used to store data (BCU
control unit only).
Check the auxiliary code. See actions
for each code below.
1 No SD card
Insert a compatible, writable SD card
into the SD CARD slot of the BCU
control unit.
2 SD card write-protected
3 SD card unreadable
A685
Power fail saving
Power fail saving is
requested too frequently
due to oscillating power
supply to the control unit.
Some of the requests may
have been discarded,
potentially causing data
loss.
Check the power supply of the control
unit. If powered internally from the
drive, check the supply voltage of the
drive.
A6A4
Motor nominal value
The motor parameters
are set incorrectly.
Check the settings of the motor
configuration parameters in group 99.
The drive is not
dimensioned correctly.
Check that the drive is sized correctly
for the motor.
A6A5
No motor data
Parameters in group 99
have not been set.
Check that all the required parameters
in group 99 have been set.
Note:
It is normal for this warning to
appear during the start-up until the
motor data is entered.
A6A6
Voltage category
unselected
The supply voltage range
has not been defined.
Define supply voltage range
(parameter
).
A6D1
FBA A parameter conflict
The drive does not have
a functionality requested
by PLC, or requested
functionality has not
been activated.
Check PLC programming.
Check settings of parameter groups
and
.
A6D2
FBA B parameter
conflict
The drive does not have
a functionality requested
by a PLC, or requested
functionality has not
been activated.
Check PLC programming.
Check settings of parameter groups
and
.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...