Fault tracing 419
AFE1
Emergency stop (off2)
Drive has received an
emergency stop (mode
selection off2) command.
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position.
Restart drive.
AFE2
Emergency stop (off1 or
off3)
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
AFEA
Enable start signal
missing
(Editable message text)
No enable start signal
received.
Check the setting of (and the source
selected by) parameter
AFEB
Run enable missing
No run enable signal is
received.
Check setting of parameter
. Switch signal on (e.g.
in the fieldbus Control Word) or check
wiring of selected source.
AFEC
External power signal
missing
is set to
but no voltage is
connected to the XPOW
connector of the control
unit.
Check the external 24 V DC power
supply to the control unit, or change the
setting of parameter
.
AFF6
Identification run
Motor ID run will occur at
next start.
Informative warning.
AFF7
Autophasing
Autophasing will occur at
next start.
Informative warning.
B5A0
STO event
Programmable event:
Safe torque off function
is active, i.e. safety
circuit signal(s)
connected to connector
XSTO is lost.
Check safety circuit connections. For
more information, see appropriate
drive hardware manual and
description of parameter
).
D200
Overtemperature
exceeded
for 5
sec or the Klixon digital
input
is false.
Check for problem in measurement
device.
Check for problem in temperature
measurement circuit.
Check well and discharge pressures
(excessive pressure can cause
heating).
Check warning function setting in
parameters.
D201
Pressure
exceeded
Analog feedback limit
delay time
is set as false.
Check for problem in measurement
device.
Check for high gas content.
Check warning function setting in
parameters.
D202
Underload
is set to warning when
actual
values are lower than
user defined curve
(parameters
-
) for
Check parameter settings.
Check setting of
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...