242 Parameters
Warning/Fault
If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
Defines the source of external event 3. See also
parameter
.
For the selections, see parameter
Selects the type of external event 3.
Fault
The external event generates a fault.
0
Warning
The external event generates a warning.
1
Warning/Fault
If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
Defines the source of external event 4. See also
parameter
.
For the selections, see parameter
Selects the type of external event 4.
Fault
The external event generates a fault.
0
Warning
The external event generates a warning.
1
Warning/Fault
If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
Defines the source of external event 5. See also
parameter
.
For the selections, see parameter
Selects the type of external event 5.
Fault
The external event generates a fault.
0
Warning
The external event generates a warning.
1
Warning/Fault
If the drive is modulating, the external event generates a
fault. Otherwise, the event generates a warning.
3
Selects the source of an external fault reset signal. The
signal resets the drive after a fault trip if the cause of the
fault no longer exists.
0 -> 1 = Reset
Note
: A fault reset from the fieldbus interface is always
observed regardless of this parameter.
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0). 10
DIO2
Digital input/output DIO2 (
, bit 1). 11
FBA A MCW bit 7
Control word bit 7 received through fieldbus interface A.
30
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...