Fuses (IEC)
aR fuses by Cooper Bussmann for protection against short-circuit in the input power cable
of drive are listed below.
Ultrarapid (aR) fuses per drive module
Fuse
Input
current
(A)
ACS880-
14-…
Size
Type Flush End
V
A
2
s
A
U
n
= 400 V
2
170M5408
690
74000
400
212
246A-3
2
170M5410
690
145000
500
257
293A-3
3
170M6410
690
210000
630
321
363A-3
3
170M6411
690
300000
700
401
442A-3
3
170M6412
690
465000
800
401
505A-3
3
170M6414
690
945000
1000
505
585A-3
3
170M6414
690
945000
1000
569
650A-3
U
n
= 500 V
1
170M4410
690
42000
315
169
240A-5
2
170M5408
690
74000
400
205
260A-5
3
170M6410
690
210000
630
257
361A-5
3
170M6411
690
300000
700
321
414A-5
3
170M6411
690
300000
700
404
460A-5
3
170M6412
690
465000
800
455
503A-5
U
n
= 690 V
1
170M4409
690
21000
250
123
142A-7
1
170M4410
690
42000
315
149
174A-7
2
170M5408
690
74000
400
186
210A-7
2
170M5410
690
145000
500
232
271A-7
3
170M6410
690
210000
630
293
330A-7
3
170M6411
690
300000
700
330
370A-7
3
170M6411
690
300000
700
375
430A-7
Note:
• See also sections:
•
Protecting the drive and the input power cable in short-circuits (page 91)
•
Protecting the drive against thermal overload (page 91)
•
Protecting the input power cable against thermal overload (page 91)
• In multicable installations, install only one fuse per phase (not one fuse per conductor).
• Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
• Fuses from other manufacturers can be used if they agree with the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
Technical data 187
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...