Harmonics are below the limits defined in IEEE 519-2014, and G5/4. The drive
complies with IEC 61000-3-2, IEC 61000-3-4 and IEC 61000-3-12.
Harmonic distortion
The table below shows typical values of the drive for short-circuit ratio (
I
sc
/
I
1
) of
20 to 100. The values will be met if the supply network voltage is not distorted by
other loads and when the drive operates at nominal load.
THDv (%)
THDi (%)
Nominal bus voltage V at PCC
< 3**
3*
V ≤ 690 V
Point on a public power supply system, electrically nearest to a particular
load, at which other loads are, or could be, connected. The PCC is a point
located upstream of the considered installation.
PCC
Indicates the total harmonic current distortion of the wave form. This value
is defined as the ratio (in %) of the harmonic current to the fundamental
(non-harmonic) current measured at a load point at the particular moment
when the measurement is taken:
THDi =
40
2
n
2
∑
I
I
1
•
100%
THDi
Indicates the total magnitude of the voltage distortion. This value is defined
as the ratio (in %) of the harmonic voltage to the fundamental (non-har-
monic) voltage:
THDv =
40
2
n
2
∑
U
U
1
•
100%
THDv
Short-circuit ratio
I
sc
/
I
1
Maximum short-circuit current at PCC
I
sc
Continuous rms input current of the drive
I
1
Amplitude of the current harmonic n
I
n
Supply voltage
U
1
Amplitude of the voltage harmonic n
U
n
* The short-circuit ratio can influence the THDi value
** Other loads can influence the THDv value
Motor connection data
Asynchronous AC induction motors, permanent magnet motors, AC induction ser-
vomotors and ABB synchronous reluctance motors (SynRM motors)
Motor types
0 to
U
1
, 3-phase symmetrical. This is indicated in the type designation label as
typical output voltage level as 3 0…
U
1
,
U
max
at the field weakening point.
Voltage (
U
2
)
0…500 Hz
Frequency (
f
2
)
Note:
Operation above 150 Hz can require type-specific derating. For more inform-
ation, contact your local ABB representative.
For drives with d
u
/d
t
filter: 120 Hz
For drives with sine filter: 120 Hz
0.01 Hz
Frequency resolution
Technical data 193
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...