• Make sure that the module does not topple over when you move it on the floor:
To open the support legs, press each leg a little down and turn it aside (1, 2). Whenever
possible secure the module also with chains.
• Do not tilt the drive module. It is heavy and its center of gravity is high. The module
overturns from a sideways tilt of 5 degrees. Do not leave the module unattended on a
sloping floor
1
2
3
3AUA0000086323
1. Stop the drive and do the steps in section
Electrical safety precautions (page 18)
before
you start the work.
2. To remove the left-hand side upper and lower front covers of the drive module, undo
the fastening screws. M4×10 combi screws, 2 N·m (18 lbf·in).
3. Disconnect the drive module busbars from the input cabling panel. Combi screw M12,
70 N·m (52 lbf·ft).
4. Disconnect the drive module busbars from the output cabling panel. Combi screw M12,
70 N·m (52 lbf·ft).
5. Remove the front air baffle.
6. See
Step-by-step drawings for an installation example of standard drive configuration
in Rittal VX25 800 mm wide enclosure (page 233)
:
• Disconnect the drive module from the LCL filter module.
• Undo the screws that attach the drive module to the enclosure frame.
• Attach the extraction ramp to the enclosure base with two screws.
7. Disconnect the power supply cable and the fiber optic cables from the external control
unit and coil them on the top of the drive module.
8. To prevent the drive module from falling, attach its top lifting lugs with chains to the
enclosure frame.
9. Pull the drive module carefully out of the enclosure preferably with help from another
person.
10. Install the new module in reverse order.
Maintenance 167
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...