Output frequency
f
Maximum output frequency with High speed mode
f
max
Nominal voltage of the drive
U
n
Continuous rms output current. No overload capability at 40 °C (104 °F).
I
n
Typical motor power in no-overload use
P
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
■
Derating for output voltage boosting
The drive can output a higher motor voltage than the supply voltage. This can require
derating of the drive output power depending on the difference between the supply voltage
and the output voltage to the motor for continuous operation.
400 V and 500 V drive types
This drawing shows the required derating for -3 and -5 (400 V and 500 V) drive types.
0.80
0.85
0.90
0.95
1.00
1.10
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
P
/
P
n
U
/
U
n
0.875
0.975
0.70
0.75
0.65
0.60
Example 1:
P
n
for ACS880-14-650A-3 is 355 kW. The input voltage (
U
) is 350 V. ->
U
/
U
n
= 350 V / 400 V = 0.875. ->
P
/
P
n
= 0.975 -> The derated power
P
= 0.975 × 355 kW =
346 kW.
To boost the output voltage to correspond the nominal supply voltage 400 V, increase the
DC voltage to 400 V × √2 × 1.03 = 582.6 V.
Example 2:
P
n
for ACS880-14-503A-5 is 355 kW. The input voltage (
U
) is 450 V. ->
U
/
U
n
= 450 V / 500 V = 0.9. ->
P
/
P
n
= 1.00 -> The derated power
P
= 1.00 × 355 kW = 355 kW.
To boost the output voltage to correspond the nominal supply voltage 500 V, increase the
DC voltage to 500 V × √2 × 1.03 = 728.3 V.
575 V and 690 V drives
This drawing shows the required derating for -7 (575 V and 690 V) drive types.
Technical data 185
Summary of Contents for ACS880-14
Page 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 14: ...14...
Page 24: ...24...
Page 30: ...30...
Page 54: ...54...
Page 64: ...64...
Page 98: ...98...
Page 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Page 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Page 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Page 150: ...150 Installation example with full cabling panels option H381...
Page 156: ...156...
Page 204: ...Standard configuration 204 Dimension drawings...
Page 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Page 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Page 208: ...LCL filter module 208 Dimension drawings...
Page 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Page 230: ...Declaration of conformity 230 The Safe torque off function...
Page 241: ...241...
Page 246: ...246...