ACS550 User’s Manual
33
Start-up, control with I/O and ID Run
Select the application macro (parameter
). The general
parameter setting procedure is given above.
The default value 1 (
ABB
STANDARD
) is suitable in most cases.
Select the motor control mode (parameter
1 (
VECTOR
:
SPEED
) is suitable in most cases. 2 (
VECTOR
:
TORQ
) is suitable for
torque control applications. 3 (
SCALAR
:
FREQ
) is recommended
• for multimotor drives when the number of the motors connected to the
drive is variable
• when the nominal current of the motor is less than 20% of the nominal
current of the drive
• when the drive is used for test purposes with no motor connected.
Enter the motor data from the motor nameplate:
Note
:
Set the motor data to
exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter
MOTOR
NOM
SPEED
to 1500 rpm results in the
wrong operation of the drive.
• motor nominal voltage (parameter
• motor nominal current (parameter
)
Allowed range: 0.2…2.0 ·
I
2hd
A
• motor nominal frequency (parameter
• motor nominal speed (parameter
• motor nominal power (parameter
REM
PAR FWD
9902
REM
PAR FWD
9904
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C3
6312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz
kW
r/min
A
cos
IA/IN t E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
supply
voltage
REM
PAR FWD
9905
REM
PAR FWD
9906
REM
PAR FWD
9907
REM
PAR FWD
9908
REM
PAR FWD
9909
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...