ACS550 User’s Manual
211
Embedded fieldbus
DCU Profile
The following tables describe the
CONTROL
WORD
content for the DCU profile.
7
RESET
0=>1
RESET
Fault reset if an active fault exists (Enter
SWITCH
-
ON
INHIBITED
). Effective if 1604 =
COMM
.
0
OPERATING
Continue normal operation
8…9 Unused
10
Unused (
ABB
DRV
LIM
)
REMOTE_CMD
(
ABB
DRV
FULL
)
1
Fieldbus control enabled.
0
• CW 0 or Ref 0: Retain last CW and Ref.
• CW = 0 and Ref = 0: Fieldbus control
enabled.
• Ref and deceleration/acceleration ramp are
locked.
11
EXT CTRL LOC
1
EXT
2
SELECT
Select external control location 2 (
EXT
2).
Effective if 1102 =
COMM
.
0
EXT
1
SELECT
Select external control location 1 (
EXT
1).
Effective if 1102 =
COMM
.
12…
15
Unused
DCU profile
CONTROL
WORD
(See parameter 0301)
Bit
Name
Value
Command/Req.
Comments
0
STOP
1
Stop
Stops according to either the stop mode
parameter or the stop mode requests (bits 7
and 8).
Simultaneous STOP and START commands
result in a stop command.
0
(no op)
1
START
1
Start
0
(no op)
2
REVERSE
1
Reverse direction
This bit XOR’d with the sign of the reference
defines direction.
0
Forward direction
3
LOCAL
1
Local mode
When the fieldbus sets this bit, it steals
control and the drive moves to fieldbus local
control mode.
0
External mode
4
RESET
-> 1
Reset
Edge sensitive.
other
(no op)
5 EXT2
1
Switch
to
EXT2
0
Switch to EXT1
6
RUN_DISABLE
1
Run disable
Inverted run enable.
0
Run enable on
7
STPMODE_R
1
Normal ramp stop
mode
0
(no op)
ABB Drives profile
CONTROL
WORD
(See parameter 5319)
Bit
Name
Value
Commanded
state
Comments
=/
=/
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...