ACS550 User’s Manual
73
Application macros
3-wire macro
This macro is used when the drive is controlled using momentary push-buttons. It
provides three (3) constant speeds. To enable, set the value of parameter 9902 to
2 (3-
WIRE
).
Note:
When the stop input (
DI
2) is deactivated (no input), the control panel start/stop
buttons are disabled.
Connection example:
Input signals
Output signals
Jumper setting
• Analog reference (AI1)
• Start, stop and direction (DI1,2,3)
• Constant speed selection (DI4,5)
• Analog output AO1: Speed
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault (-1)
or
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
External speed reference 1:
0
…
10 V
Reference voltage 10 V DC
Motor output speed:
0
…
20 mA
Constant speed selection
1
Constant speed selection
1
Relay output 1, programmable
Default operation:
Relay output 2, programmable
Default operation:
Relay output 3, programmable
Default operation:
Output current:
0
…
20 mA
Ready
=>19 connected to 21
Running
=>22 connected to 24
Fault (-1)
=>25 connected to 27
Analog input circuit common
Not used
Analog output circuit common
Auxiliary voltage 24 V DC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
Note 1.
Code:
0 = open, 1 = connected
DI4 DI5
Output
0
0
Reference through AI1
1
0
CONST
SPEED
1 (1202)
0
1
CONST
SPEED
2 (1203)
1
1
CONST
SPEED
3 (1204)
Start:
Momentary activation with DI2 activated starts the drive
Stop:
Momentary deactivation stops the drive
Fwd/Rev:
Activation reverses rotation direction
Not used
(Fault => 25 connected to 26)
X1
1…10 kohm
J1
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
12
J1
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...