The many variables in the last requirement above are most easily dealt with using
the following tables.
• First, determine your maximum braking time ON (ON
MAX
), minimum braking time
OFF (OFF
MIN
) and load type (deceleration or overhauling load).
• Calculate duty cycle:
• In the appropriate table, find the column that best matches your data:
– ON
MAX
< column specification and
– Duty cycle < column specification
• Find the row that matches your drive.
• The minimum power rating for deceleration to zero is the value in the selected
row/column.
• For overhauling loads, double the rating in the selected row/column, or use the
“Continuous ON” column.
208…240 V drives
Type code
ACS550-
01/U1-
see below
Resistance
Resistor
1
minimum continuous power rating
Deceleration-to-zero rating
P
rcont
Continuous ON
> 60 s ON
> 25% Duty
R
MAX
R
MIN
P
r3
< 3 s ON
> 27 s OFF
< 10% Duty
P
r10
< 10 s ON
> 50 s OFF
< 17% Duty
P
r30
< 30 s ON
> 180 s OFF
< 14% Duty
P
r60
< 60 s ON
> 180 s OFF
< 25% Duty
ohm
ohm
W
W
W
W
W
Three-phase supply voltage,
208…240 V
-04A6-2
234
80
45
80
120
200
1100
-06A6-2
160
80
65
120
175
280
1500
-07A5-2
117
44
85
160
235
390
2200
-012A-2
80
44
125
235
345
570
3000
-017A-2
48
44
210
390
575
950
4000
-024A-2
32
30
315
590
860
1425
5500
-031A-2
23
22
430
800
1175
1940
7500
1
Resistor time constant specification must be > 85 seconds.
Time
Power
Deceleration curve
Overhauling load
curve
Time
Temperature
Avg. braking power
during deceleration
Avg. braking power –
overhauling load
x
2x
to zero
Duty cycle
=
(ON
MAX
+ OFF
MIN
)
· 100%
ON
MAX
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...