ACS550 User’s Manual
253
Diagnostics
Alarm codes (Basic Control Panel)
The Basic Control Panel indicates control panel alarms with a code, A5xxx. The
following table lists the alarm codes and descriptions.
2027
USER
LOAD
CURVE
This alarm warns that the condition defined by parameter 3701
USER
LOAD
C
MODE
has been valid longer than half of the time defined by
3703
USER
LOAD
C
TIME
.
2028
START
DELAY
Shown during the Start delay. See parameter 2113
START
DELAY
.
Note 1.
Even when the relay output is configured to indicate alarm conditions (e.g. parameter
1401
RELAY OUTPUT
1 = 5 (
ALARM
) or 16 (
FLT
/
ALARM
)), this alarm is not indicated by a relay
output.
Code
Description
5001
Drive is not responding.
5002
The communication profile is incompatible with the drive.
5010
The panel’s parameter backup file is corrupted.
5011
Drive is controlled from another source.
5012
Rotation direction is locked.
5013
Button is disabled, because start is inhibited.
5014
Button is disabled, because drive is faulted.
5015
Button is disabled, because local mode lock is on.
5018
Parameter default value can’t be found.
5019
Writing a non-zero value is prohibited (can only write a zero value).
5020
Group or parameter does not exist or parameter value is inconsistent.
5021
Group or parameter is hidden.
5022
Group or parameter is write protected.
5023
Modification is not allowed while the drive is running.
5024
Drive is busy, try again.
5025
Write is not allowed while upload or download is in progress.
5026
Value is at or below low limit.
5027
Value is at or above high limit.
5028
Value is invalid – doesn't match any values in the discrete values list.
5029
Memory is not ready, try again.
5030
Request is invalid.
5031
Drive is not ready, e.g due to low DC voltage.
5032
Parameter error was detected.
5040
Selected parameter set can’t be found in the current parameter backup.
5041
Parameter backup doesn't fit into memory.
5042
Selected parameter set can’t be found in the current parameter backup.
5043
No start inhibit was granted.
5044
Parameter backup versions do not match.
Alarm
code
Display
Description
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...