ACS550 User’s Manual
235
Fieldbus adapter
The state diagram below describes the start-stop function of
CONTROL
WORD
(CW)
and
STATUS
WORD
(SW) bits.
(CW xxxx x1xx xxxx x110)
MAINS OFF
Power ON
(CW Bit0=0)
(SW Bit6=1)
(SW Bit0=0)
From any state
n(f)=0 / I=0
OFF1 (CW Bit0=0)
A
C D
(CW Bit3=0)
(SW Bit2=0)
(SW Bit0=1)
(CW= xxxx x1xx xxxx x111)
(SW Bit1=1)
(CW Bit3=1 and
(CW Bit4=0)
n(f)=0 / I=0
From any state
SWITCH-ON
INHIBITED
NOT READY
TO SWITCH ON
OPERATION
INHIBITED
READY TO
SWITCH ON
READY TO
OPERATE
RFG OUTPUT
ENABLED
C D
From any state
Emergency Off
OFF2 (CW Bit1=0)
(SW Bit4=0)
OFF2
ACTIVE
From any state
Fault
(SW Bit3=1)
FAULT
(CW Bit7=1)
(SW Bit5=0)
Emergency Stop
OFF3 (CW Bit2=0)
SW Bit12=1)
RFG: ACCELERATOR
ENABLED
(CW=xxxx x1xx xx11 1111)
(CW Bit6=0)
C
(CW=xxxx x1xx x111 1111)
(SW Bit8=1)
D
B
D
OPERATING
OFF3
ACTIVE
KEY
State
State change
CW =
CONTROL
WORD
SW =
STATUS
WORD
RFG = Ramp Function Generator
I = Param. 0104
CURRENT
f = Param. 0103
OUTPUT
FREQ
n = Speed
(SW Bit2=1)
OPERATION
ENABLED
(CW=xxxx x1xx xxx1 1111)
A
(CW Bit5=0)
C D
B
B
(SW Bit1=0)
OFF1
ACTIVE
OPERATION
INHIBITED
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...