• relay output states, numbered sequentially beginning with coil 00033.
The following table summarizes the 0xxxx reference set:
For the 0xxxx registers:
• Status is always readable.
• Forcing is allowed by user configuration of the drive for fieldbus control.
• Additional relay outputs are added sequentially.
Modbus
ref.
Internal location
(all profiles)
ABB
DRV
LIM
(5305 = 0)
DCU
PROFILE
(5305 = 1)
ABB
DRV
FULL
(5305 = 2)
0
0001
CONTROL
WORD
– Bit 0
OFF1
1
STOP
OFF1
1
0
0002
CONTROL
WORD
– Bit 1
OFF2
1
START
OFF2
1
0
0003
CONTROL
WORD
– Bit 2
OFF3
1
REVERSE
OFF3
1
0
0004
CONTROL
WORD
– Bit 3
START
LOCAL
START
0
0005
CONTROL
WORD
– Bit 4
N/A
RESET
RAMP_OUT_ZERO
1
0
0006
CONTROL
WORD
– Bit 5
RAMP_HOLD
1
EXT2
RAMP_HOLD
1
0
0007
CONTROL
WORD
– Bit 6
RAMP_IN_ZERO
1
RUN_DISABLE
RAMP_IN_ZERO
1
0
0008
CONTROL
WORD
– Bit 7
RESET
STPMODE_R
RESET
0
0009
CONTROL
WORD
– Bit 8
N/A
STPMODE_EM
N/A
0
0010
CONTROL
WORD
– Bit 9
N/A
STPMODE_C
N/A
0
0011
CONTROL
WORD
– Bit 10 N/A
RAMP_2
REMOTE_CMD
1
0
0012
CONTROL
WORD
– Bit 11 EXT2
RAMP_OUT_0
EXT2
0
0013
CONTROL
WORD
– Bit 12 N/A
RAMP_HOLD
N/A
0
0014
CONTROL
WORD
– Bit 13 N/A
RAMP_IN_0
N/A
0
0015
CONTROL
WORD
– Bit 14 N/A
REQ_LOCALLOCK N/A
0
0016
CONTROL
WORD
– Bit 15 N/A
TORQLIM2
N/A
0
0017
CONTROL
WORD
– Bit 16 Does not apply
FBLOCAL_CTL
Does not apply
0
0018
CONTROL
WORD
– Bit 17
FBLOCAL_REF
0
0019
CONTROL
WORD
– Bit 18
START_DISABLE1
0
0020
CONTROL
WORD
– Bit 19
START_DISABLE2
0
0021…
0
0032
Reserved
Reserved
Reserved
Reserved
0
0033
RELAY
OUTPUT
1
Relay Output 1
Relay Output 1
Relay Output 1
0
0034
RELAY
OUTPUT
2
Relay Output 2
Relay Output 2
Relay Output 2
0
0035
RELAY
OUTPUT
3
Relay Output 3
Relay Output 3
Relay Output 3
0
0036
RELAY
OUTPUT
4
Relay Output 4
Relay Output 4
Relay Output 4
0
0037
RELAY
OUTPUT
5
Relay Output 5
Relay Output 5
Relay Output 5
0
0038
RELAY
OUTPUT
6
Relay Output 6
Relay Output 6
Relay Output 6
1
= Active low
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...