194
ACS550 User’s Manual
Embedded fieldbus
Input reference select
Using the fieldbus to provide input references to the drive requires:
• drive parameter values set as defined below
• fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Reference Scaling
Where required,
REFERENCES
can be scaled. See the following, as appropriate:
• Modbus Register
in section
Modbus protocol technical data
on page
•
in section
ABB control profiles technical data
on page
Miscellaneous drive control
Using the fieldbus for miscellaneous drive control requires:
• drive parameter values set as defined below
• fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter
Value
Description
Modbus protocol
reference
ABB
DRV
DCU
PROFILE
1102
EXT
1/
EXT
2
SEL
8 (
COMM
) Reference set selection by fieldbus.
40001 bit 11
40031 bit 5
1103
REF
1
SELECT
8 (
COMM
) Input reference 1 by fieldbus.
40002
1106
REF
2
SELECT
8 (
COMM
) Input reference 2 by fieldbus.
40003
Drive parameter
Value
Description
Modbus
protocol
reference
ABB
DRV
DCU
PROFILE
1601
RUN
ENABLE
7 (
COMM
) Run enable by fieldbus.
40001 bit 3 40031 bit 6
(inverted)
1604
FAULT
RESET
SEL
8 (
COMM
) Fault reset by fieldbus.
40001 bit 7 40031 bit 4
1606
LOCAL
LOCK
8 (
COMM
) Source for local lock selection is
the fieldbus.
Does not
apply
40031 bit 14
1607
PARAM
SAVE
1 (
SAVE
)
Saves altered parameters to
memory (then value returns to 0).
41607
1608
START
ENABLE
1
7 (
COMM
) Source for start enable 1 is the
fieldbus Command word.
Does not
apply.
40032 bit 2
1609
START
ENABLE
2
7 (
COMM
) Source for start enable 2 is the
fieldbus Command word.
40032 bit 3
2013
MIN
TORQUE
SEL
7 (
COMM
) Source for minimum torque
selection is the fieldbus.
40031 bit 15
2014
MAX
TORQUE
SEL
7 (
COMM
) Source for maximum torque
selection is the fieldbus.
2201
ACC
/
DEC
1/2
SEL
7 (
COMM
) Source for ramp pair selection is
the fieldbus.
40031 bit 10
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...